SONG Haihua1, WANG Bochun1, ZHOU Jun2 1.Testing and Research Institute under Hunan Provincial Electric Power Company. ANALYSIS AND OPTIMIZATION OF COORDINATED CONTROL SYSTEM FOR SUPERCRITICAL 600 MW UNIT[J]. Thermal power generation, 2011, 40(7): 70-73.
SONG Haihua1, WANG Bochun1, ZHOU Jun2 1.Testing and Research Institute under Hunan Provincial Electric Power Company. ANALYSIS AND OPTIMIZATION OF COORDINATED CONTROL SYSTEM FOR SUPERCRITICAL 600 MW UNIT[J]. Thermal power generation, 2011, 40(7): 70-73.DOI:
Through analysis of problems existing in original coordinated control system of a supercritical unit equipped with direct injection coal pulverizing system using double-inlet and double-outlet ball mills
i.e.the AGC load changing rate of 6 MW/min is unable to be satisfied
the regulating behavior of once-through boiler boasting non-linearity
the temperature at midle points having deviation etc.
an optimization scheme
including adding front feed to load-changing commands
adding non-linear function and parameter varying device in the power-adjusting circuits of combustion
feed-water
and coodinated control
has been put forward and tests of increasing and decreasing load under AGC mode being carried out
it shows that the coordinated control system after optimization can satisfy the requirements of assessment indices for automatic generation control(AGC)