330MW机组凝结水泵变频改造及系统运行优化
摘要
国电菏泽电厂三期330 MW机组凝结水泵(凝泵)实施变频改造后
为了进一步降低凝结水管道的压力损失
机组正常运行时全开除氧器水位主、副调节阀及其旁路电动阀。为了满足汽动给水泵(汽泵)密封水压力的需要
适当开启汽泵密封水旁路阀
同时对凝结水系统控制逻辑进行了优化。优化后凝泵在变频运行方式下节电效果明显
机组安全性得到进一步提高。
Abstract
After implementation of frequency conversion retrofit for condensate pumps of 330 MW untis in the third-phase poject of Guodian Heze Power Plant
in order to further reduce the pressure loss in the condensate pipeline
the main and auxiliary regulating valves for water-level in the deaerator as well as its bypass motor-operated valve are fully opened during normal operation of units.For satisfying the requirement of sealing water pressure in the turbine-driven feed-water pump
the sealing water bypass valve of turbine-driven feed-water pump has to be properly opened.At the same time
the control logic of condensate system has been optimized.After optimization
the effectivenes of electricity-saving is remarkable under operation mode of frequency conversion