XU Ling1, KONG Shengjie1, YU Wanqing2, et al. SELECTION OF OPTIMAL STANDARD DILUENT OF FUROL FOR DETECTING FUROL IN TRANSFORMER OIL BY USING HIGHLY EFFECTIVE LIQUID-PHASE CHROMATOGRAPHIC METHOD[J]. Thermal power generation, 2011, 40(9): 38-41.
XU Ling1, KONG Shengjie1, YU Wanqing2, et al. SELECTION OF OPTIMAL STANDARD DILUENT OF FUROL FOR DETECTING FUROL IN TRANSFORMER OIL BY USING HIGHLY EFFECTIVE LIQUID-PHASE CHROMATOGRAPHIC METHOD[J]. Thermal power generation, 2011, 40(9): 38-41.DOI:
The furol's standard solution diluent used in detecting furol content in transformer oil by adopting highly effective liquid-phase chromatographic method has remarkable influence upon the result of analysis.In order to screen out the standard solution diluent of furol
four kinds of diluents
namely new basic oil(not processed)
new transformer oil no.45
new transformer oil no.25
and pure methanol
have been tested.Results of test show that the influence of using new transformer oil no.45 as standard solution diluent of furol has the smallest effect upon the result of furol analysis
the detected result has high accuracy
and good repeatability
and good linearity in a range of 0~10.00 mg/L.Taking new transformer oil no.45 as standard solutaion diluent of furol
the furol content in oilsamples for nearly 30 transformers has been analysed by adopting the highly effective liquid-phase chromato graphic method
the results of analysis fully tally with the requirements specified in the 《Guidance for judging the insulation aging of oil-inmersed transformers》.