Directing against the problems existing in the control system of CFB boiler for 330 MW unit equipped in Jinghai Gangue Power Generation Co Ltd
such as bad adaptability to coal quality variation
frequent actuation of the furnace pressure protection
and non-accurate set value of secondary air flow rate
etc.
the coefficient of feed forward magnitude has been corrected.Through links of inertance
the optimization measures in load-increasing and load-reducing
i.e.increasing the air flow rate at first
and then increasing the coal feed rate;and reducing the coal feed rate at first
and then reducing the air flow rate
have been realized.Test in load change of the unit shows that the regulating performance and quality of said control system after optimization all suatisfy the requirements of control