LUO Xiaolin Guangxi Laibin Sinoki Power Generation Co Ltd. ANALYSIS AND DISPOSAL OF VIBRATION FAULT ON ONE 2446B/1201 TYPE PULVERIZED COAL EXHAUSTERS[J]. Thermal power generation, 2012, 41(2): 84-87.
LUO Xiaolin Guangxi Laibin Sinoki Power Generation Co Ltd. ANALYSIS AND DISPOSAL OF VIBRATION FAULT ON ONE 2446B/1201 TYPE PULVERIZED COAL EXHAUSTERS[J]. Thermal power generation, 2012, 41(2): 84-87.DOI:
某台2246B/1201型排粉机振动故障分析与处理
摘要
某电厂2×360MW机组锅炉排粉机运行中出现轴承轴向振动故障
解体检修发现振动故障是排粉机运行过程中2号轴承的内圈与轴颈配合出现松动
造成轴颈和轴凸肩摩擦、轴承内圈与轴颈磨损所致。更换排粉机全套转轴和轴承后故障消除
运行中轴承振动均处于良好状态。
Abstract
The axial vibration fault has occurred in operation of the pulverized coal exhausters equipped for boilers of 2×360 MW units.It is discovered in disassembiling repair that the looseness in fit between the inner sleeve of bearing no2 and the shaft neck appeared in operation is the cause leading to vibration fault
resulting in rubbing between the shaft neck and the raised soulder of shaft due to abrasion of inner sleeve of the bearing and main shaft.After replacing the whole set of rotary shaft and bearings
the vibration fault has been eliminated
the vibration of bearings in operation of the exhauster being in a good situation.