LI Yu1, CHU Chanqi2, FAN Dian3, et al. CONNECTION AND CONTROL LOGIC CONFIGURATION BETWEEN IMPORTED DEVICES AND PROFIBUS MASTER STATION IN FCS165 FIELDBUS CONTROL SYSTEM[J]. Thermal power generation, 2012, 41(10): 66-68.
LI Yu1, CHU Chanqi2, FAN Dian3, et al. CONNECTION AND CONTROL LOGIC CONFIGURATION BETWEEN IMPORTED DEVICES AND PROFIBUS MASTER STATION IN FCS165 FIELDBUS CONTROL SYSTEM[J]. Thermal power generation, 2012, 41(10): 66-68.DOI:
Based on plant-wide and successful application of the FCS165 field bus control system on integrated control of the supercritical 2×600 MW air cooled unit for Qinling Power Plant
the method of connecting the Profibus master station in FCS165 field bus control system to the ACS510 series frequency converter(slave station) from ABB Company of America was introduced.Moreover
the configuration and parameters setting for communication between master and slave station were also presented.Besides
problems occurred during debugging of the system mentioned was analyzed and the countermeasures were given.