ZHANG Xiaohui1, JIA Huanzhong2, GUO Min2, et al. STUDY ON COORDINATED CONTROL SYSTEM OF UNITS EQUIPPED WITH CFB BOILER[J]. Thermal power generation, 2012, 41(5): 87-91.
ZHANG Xiaohui1, JIA Huanzhong2, GUO Min2, et al. STUDY ON COORDINATED CONTROL SYSTEM OF UNITS EQUIPPED WITH CFB BOILER[J]. Thermal power generation, 2012, 41(5): 87-91.DOI:
Directing against the complex process in combustion
heat transfer
and flow
a decoupling control taking the coal quantity as the main to regulate the pressure in boiler drum and using the air quantity to control the bed temperature has been put forward
and the coordinated control strategy with prediction specialist control and with rapid correct circuit of variable amplitude and variable time being adopted.The application of said control on one CFB boiler of 135 MW unit shows that the main parameters of said unit
such as the actual load command of unit
the actual load of unit
the pressure before unit
the pressure command before unit
the pressure in boiler drum
the total fuel quantity
and the total air quantity etc.
all are more stable during the time of static and dynamic state.The problems of non-linearity
multi-variable
and time-varying behavior
and large retardation of objects with complex process having been better resolved.