MA Chong, CHEN Shaoyu Technical Center of Tianjin Electric Power Corporation. LEAKAGE OF HEAT EXCHANGE TUBE IN A HEATING NETWORK: REASON ANALYSIS AND TREATMENT[J]. Thermal power generation, 2012, 41(10): 75-77.
MA Chong, CHEN Shaoyu Technical Center of Tianjin Electric Power Corporation. LEAKAGE OF HEAT EXCHANGE TUBE IN A HEATING NETWORK: REASON ANALYSIS AND TREATMENT[J]. Thermal power generation, 2012, 41(10): 75-77.DOI:
The stainless steel heat exchange tube in a heating network was cracked and leakage happened only after one and a half year's operation.Based on a series of tests on the cracked pipe
such as macroscopic examination
chemical composition analysis
metallographic analysis
electron microscopic and energy spectrum analysis
stress corrosion cracking was considered as the main reason for tube leakage.Thus
to prevent the heat exchange tube from cracking
it is suggested that indexes like Cl-concentration
dissolved oxygen content and the water hardness of the heating network should be strictly controlled;the heat exchange tube should be washed by using demineralized water as soon as the heater stopped working
so as to decrease the Cl-concentration inside the pipe wall;the tube should be protected by filling with nitrogen instead of water.