YIN Zun Xi’an Thermal Power Research Institute Co.. Reason analysis on tube burst in water wall of an ultra supercritical 1 000MW unit[J]. Thermal power generation, 2013, 42(7): 92-96.
YIN Zun Xi’an Thermal Power Research Institute Co.. Reason analysis on tube burst in water wall of an ultra supercritical 1 000MW unit[J]. Thermal power generation, 2013, 42(7): 92-96.DOI:
Several tests were performed on the burst tubes of No.1boiler in Huaneng Yuhuan Power Plant
such as chemical composition analysis
metallographic structure examination
hardness test
room temperature tensile test
room temperature impact test and energy disperse spectrum analysis(EDS).The results showed that
the tube burst occurred on water wall resulted from short-term overheating.The abnormal working conditions like blocking in water wall tubes or poor water circulation were considered as the basic reason for instantaneous overheating of the water wall tubes.Besides
the over-temperature running of tubes
high content of corrosive element S in coal and reducing atmosphere due to incomplete combustion accelerated the failure of water wall tubes.In order to avoid the similar tube burst problems
appropriate recommendations such as enhancing the operation monitoring and controlling the oxygen and sulfur content in coal into the furnace were put forward.