ZHAO Zhidan, GU Tao, CHEN Zhigang, et al. Optimization on coordinated control system of supercritical unit in Huaneng Shanghai Shidongkou Second Power Plant[J]. Thermal power generation, 2014, 43(2): 117-121.
ZHAO Zhidan, GU Tao, CHEN Zhigang, et al. Optimization on coordinated control system of supercritical unit in Huaneng Shanghai Shidongkou Second Power Plant[J]. Thermal power generation, 2014, 43(2): 117-121.DOI:
In the No.1and No.2supercritical 600 MW units in Huaneng Shanghai Shidongkou Second Power Plant
under the unit automatic generation control(AGC)
large control deviation of the main steam temperature
main steam pressure and superheating ratio at steam separator intermediate point resulted in low input ratio of the AGC.Combining with the operation situation of the unit
optimization on control logic of several subsystems was performed
such as the unit coordinated control system
the main and reheat steam temperature control system
and the feed flow rate control system.The variable load test with load variation rate of 1.5%/min was conducted on the optimized control system.The results show that
the absolute values of the main steam temperature deviation of the two units during load variation are both below 5 ℃
that of the reheat steam temperature are below 10℃
and that of the superheating ratio at steam separator intermediate point are below 6superheating ratio at steam separator intermediate point.Moreover
the absolute value of the main steam pressure deviation of the two units are both less than 0.6MPa
and that of the power are less than 2MW
indicating the optimized control system makes the fluctuation of the steam turbine regulating valve opening small