LI Yan, YANG Zhongcan, CHEN Hongwei, et al. Experimental study on low NOx combustion system retrofitting in a 150MW unit boiler[J]. Thermal power generation, 2014, 43(8): 105-110.
LI Yan, YANG Zhongcan, CHEN Hongwei, et al. Experimental study on low NOx combustion system retrofitting in a 150MW unit boiler[J]. Thermal power generation, 2014, 43(8): 105-110.DOI:
In order to reduce the NOxemission and inhibit coking in boiler furnace
transformation was carried out on a 480t/h tangentially fired boiler
by using the technology combining the fuel-staged combustion technology with installation of the separated over firing air(SOFA)nozzles above the highest secondary air nozzles.Moreover
combustion optimization and regulation tests were performed after the retrofitting.The results indicate that:the NOxemission decreased to lower than 250mg/m3(by 55%)when the SOFA damper opened with two layers and with opening degree of 55%;when burning Wucaiwan coal
the boiler had efficiency higher than 92%
and the optimal efficiency reached up to 92.48%
about 0.79%higher than that before the retrofitting;the exhaust temperature was lower than 850℃
which can prevent the boiler from coking on heating surface effectively
and ensure the economy and safety of boiler operation.