On the basis of the typical feed water systems in heat recovery steam generators(HRSG)on 9F class gas-turbine combined units manufactured by SMS
GE and MHI GT
relative comparisons were carried out
from such aspects as feed water oxygen content adaptability
system complexity degree
system operation safety and economy.It suggests that the deaerating condenser or condenser equipped with bypass deaerating system should be adopted at the unit side
to ensure the oxygen content in HRSG feedwater satisfy the requirements under any conditions.A feed water system that is more suitable for unit under full condensing condition was selected.Furthermore
combined with the special requirements of heating supply unit on feed water system
the current feed water systems of heat supply units were analyzed and the optimized feed water system was proposed.