HUANG Yuanping, WU Lin, XU Zhiming. Experimental study on microbial fouling and corrosion on heat exchangers surface in power plants[J]. Thermal power generation, 2015, 44(6): 111-116.
HUANG Yuanping, WU Lin, XU Zhiming. Experimental study on microbial fouling and corrosion on heat exchangers surface in power plants[J]. Thermal power generation, 2015, 44(6): 111-116.DOI:
In order to study the characteristics of microbial fouling on heat exchangers
the iron bacteria that is easy to form microbial fouling in the industrial circulating cooling water was selected to conduct static microbial fouling experiments.The low carbon steel pieces before and after experiment was analyzed by scanning electron microscopy.The gravimetric method was taken to record the changes of fouling.The optical turbidity was taken to record the number changes of bacteria.The results show that
the corrosion on low carbon steel was slight in the water environment
and iron bacteria can increase the corrosion dramatically.The iron bacteria can cause severe corrosion and microbial fouling on the surface of low carbon steel.Microbial fouling and microbial corrosion occurred simultaneously.When the effect of fouling was greater than that of corrosion