DU Zhihua, YAO Wei, FANG Shunli, et al. Investigation on slagging problem occurred on a 350MW boiler co-fring Zhundong coal[J]. Thermal power generation, 2015, 44(11): 109-113.
DU Zhihua, YAO Wei, FANG Shunli, et al. Investigation on slagging problem occurred on a 350MW boiler co-fring Zhundong coal[J]. Thermal power generation, 2015, 44(11): 109-113.DOI:
Zhundong-coal from Wucaiwan is highly inflammable and easily burnt out
which has excellent combustion properties.However
this kind of coal has the characteristic of serious slagging
because of the high content of sodium and calcium in the coal ash.Thus
taking No.2unit in Zhundong Wucaiwan Power Plant as the research object
this article numerically simulated the temperature field and pulverized coal particle flow characteristics in furnace of the opposed firing boiler equipped with swirling burners.The results show that
the swirl strength of the secondary air outside the rear-wall burner was too large
causing an over high flue gas temperature around water wall at the rear-wall.Due to the hot gas flow
the pulverized coal flowing from the D layer burners got close to the walls
thus the slagging on the rear-wall became serious
and the safe and economic operation of the boiler firing Zhundong coal was greatly affected.Therefore
during combustion of Zhundong coal
to ease the slagging
it is better to carry out load disturbance according to the actual situations
or co-fire the coals with low sodium content from the lower layer(layer A or B)mills.