ZHANG Li, ZENG Shenfu, CHENG Haoran, et al. Discussions on tube bundle arrangement factor for condensers in steam turbines[J]. Thermal power generation, 2016, 45(10): 110-114.
ZHANG Li, ZENG Shenfu, CHENG Haoran, et al. Discussions on tube bundle arrangement factor for condensers in steam turbines[J]. Thermal power generation, 2016, 45(10): 110-114.DOI:
Combined with four calculation methods for average heat transfer coefficient of the condensers
the feasibility and rationality of the calculation methods for tube bundle arrangement factor was further discussed.A calculation method which has operability was proposed.Moreover
taking condensers in300 MW units as the example
the tube bundle arrangement correction factors of four tube bundles were calculated
such as the radial inflow ovoid tube bundle
the deformation form of the TEPEE tube bundle
the disguised tree tube bundle and the narrowband downstream tube bundle with double trapezoidal air cooling zone.The values were 1.082
1.038
1.094 and 1.169
respectively.The calculation result indicate the condenser using the narrowband downstream tube bundle with double trapezoidal air cooling zone has the optimal condensing heat transfer performance.