HUANG Zhong, GUO Taixing, LIANG Jinlin, et al. Uniformity improvement for bed temperature of a 300MW unit CFB boiler[J]. Thermal power generation, 2016, 45(11): 68-74.
HUANG Zhong, GUO Taixing, LIANG Jinlin, et al. Uniformity improvement for bed temperature of a 300MW unit CFB boiler[J]. Thermal power generation, 2016, 45(11): 68-74.DOI:
several problems occur in large number of 300 MW unit CFB boilers
such as large bed temperature deviations
existence of local high temperature points and relatively high original emission concentration of SO2 and NOx
which brings difficulties in energy saving
cost reducing and ultra-low emission of the CFB boilers.Analysis shows that
the deviations of separator flow and efficiency result in deviations between the circulation volume and the material concentration in the circulation loop
thus bring the temperature deviation at both sides and middle part of the bed.The temperature deviation can be avoided by retrofitting the separator inlet gas flue and cyclone vortex
which would contribute to a more even coal supply.After transformation
the average bed temperature decreased by more than 35℃
and the consumptions of the desulfurizer and denitration urea are reduced by 40% and 20%