In the combined system of low temperature economizer and air heater
the heater usually can not be put into operation after the low temperature economizer stopped running. To solve this problem
a separated system combing the low temperature economizer with the air heater was proposed. In this system
the low temperature economizer and the air heater are two independent systems
the air heater is heated by No.7 extraction steam
which reduces the quality of the air heater's heat source. At the same time
the spraying system absorbs the heat of part of the exhaust steam
which increases the coal saving capacity. Taking a 600 MW unit in Inner Mongolia as the example
economic analysis for the separated system
combined system and the conventional low temperature economizer system were carried out. The results show that
the energy conservation potential of the separated system was 1.46 g/(k W·h) and 0.46 g/(k W·h) higher than that of the pure low temperature economizer system and the combined system
respectively. For the separated system
the energy conservation potential was better at lower load. In the spraying system
the energy conservation potential was better at higher environmental temperature