LUO Richeng, LI Wen, LI Zhiqian, et al. Modeling of Wind Turbine Generator Based on Piecewise Parameter and Its Lightning Transient Overvoltage Analysis[J]. 2015, 41(8): 2780-2787.
LUO Richeng, LI Wen, LI Zhiqian, et al. Modeling of Wind Turbine Generator Based on Piecewise Parameter and Its Lightning Transient Overvoltage Analysis[J]. 2015, 41(8): 2780-2787.DOI:
Lightning stroke is one of the most important influences on secure running of wind turbine generator(WTG). The base of wind turbine
the core of internal controlling cable
and the cable shielding layer will generate induced voltage when the WTG suffers from lightning stroke. Considering electro-magnetic inducted voltages of inductance and capacitance
we build an equivalent model including wind turbine blade
tower and signal cable to study transient overvoltage caused by lightning stroke better. Furthermore
the simulation is conducted by utilizing ATP/EMTP electro-magnetic transient simulator. Finally
we analyze the influence of wind turbine signal cable on induction voltage by three factors
such as the wind turbine grounding resistance
the lightning current waveform
and the height of tower. The results show that wave head time is inversely proportional to voltage
when wave head time is 1.2 μs
voltage difference in the top of the tower is 1 611.6 times larger than 20 μs; the higher tower is
the greater the voltage difference is; grounding resistance is proportional to the ground potential of tower base
when the grounding resistance is 10 ?
the voltage of tower base is 8.4 times larger than 1 Ω.