Modular multilevel converters(MMCs) have been increasingly used in power systems. Their main circuit parameter design determines the initial cost and performance of the systems using them. We have studied the parameter design of several important components of the main circuit of MMC
such as link transformers
arm reactors
sub-module capacitors
and IGBT modules. Firstly
based on the fundamental equivalent circuit of MMC
a method is proposed for the determining the rated no-load voltage of link transformer at valve side
which further confirms that the range of(1.00
1
.05)/2 times of the voltage should be selected at DC side. Secondly
by introducing the concept of equivalent capacity dischar
ging time constant
it is found that the fluctuation ratio of sub-module capacitor voltage varies with the time constant in a relationship that rarely changes for different projects
therefore
the time constant is universally applicable and the general parameters of sub-module capacitors can be obtained accordingly. Analyzing several practical projects
we have obtained a recommended value of the equivalent capacity discharging time constant
which is 40 ms. Thirdly
the voltage and current load of sub-module power electronic devices under four extreme operating conditions are investigated using analytical formulae of the MMC. It is discovered that the current load changes greatly according to the operating condition. Finally
by introducing the concepts of phase unit series resonance angle frequency and circulating current resonance angle frequency
we have established a principle for determining the parameters of arm reactor
and through analyzing some corresponding parameters of existing projects
the recommended value of phase unit series resonance angle frequency is given as the rated angle frequency of connected power system.