LE Yanjie, XUAN Yaowei, YU Enke, et al. Study on Lightning Impulse Test for DC Power Cable Under Different Connection Ways[J]. 2015, 41(8): 2723-2731.DOI:
the measured voltage waveform has abnormal jitter and does not accord with the standards. To solve this problem
we theoretically analyzed the impulse test discharge circuit with its impulse voltage generator connecting firstly to the voltage divider and then to the test object(defined as "Way Ⅰ"). We also simulated the circuit in Way I in Pspice
and compared and simulated the waveforms obtained from the capacitive voltage divider and the test object. The analysis indicates that the lead inductance between the capacitive voltage and the test cable leads to the deviance of the measured waveform from the actual waveform or even the abnormal jitter
if the lead inductance is large enough. Hence
we proposed a circuit that has the impulse voltage generator connected first to test object and then to voltage divider(defined as "Way Ⅱ"). To verify Way Ⅱ
using various lead inductances
we compared the coincidence degree between the measured waveforms using the two circuits and the actual waveform
as well as the measuring error of some time parameters(front time
time to half-value). The result indicates that using Way Ⅰ
with increasing lead inductance
the measured waveform deviation
the amplitude of abnormal jitter
and the measuring error of time parameters all increases. However
using Way Ⅱ
even with a relatively high lead inductance
the measured waveform has no abnormal jitter and it is nearly consistent with the actual one
while the measuring error is small. In addition
we conducted the experimental lightning impulse tests using Way Ⅱ. The obtained test waveform has no abnormal jitter and it is consistent with the simulation result.