UHF partial discharge(PD) detection technology has been widely used
but it is still lacking in effective and unified principles on performance calibration of the UHF PD detection system. In order to quantitatively calibrate the characteristics of the UHF sensor and detection system
the calibration platform of partial discharge UHF detection based on gigahertz transverse electromagnetic(GTEM) cell was designed
and the effects of three factors on the structure of a typical installation of sensors and detection system performance were studied. The results show that the impact sensor mounting structure on the actual reception performance is very significant
in the range of 300
1
500 MHz
three sensors mounting structure equivalent height are 10.8 mm
10.2 mm
and 3.3 mm
respectively. Sensitivity of
corresponding UHF detection systems are 2.8 μV/mm
2.9 μV/mm and 36.7 μV/mm
respectively
the difference is significant. So
sensor mounting structure factors specific integrated assessment must be considered in sensor calibration and evaluation of UHF partial discharge detection system performance.