YANG Yanhong, PEI Wei, DENG Wei, et al. Method for Calculating Power Flow of Hybrid AC/DC Power Distribution System with Converter Station Operation Mode[J]. 2016, 42(7): 2149-2157.
YANG Yanhong, PEI Wei, DENG Wei, et al. Method for Calculating Power Flow of Hybrid AC/DC Power Distribution System with Converter Station Operation Mode[J]. 2016, 42(7): 2149-2157.DOI:
In accordance with multi-terminal direct current(VSC-MTDC) structure hybrid AC/DC power distribution system
considering AC side three-phase unbalance model and VSC converter operation control mode simultaneously
we proposed a sequential AC/DC power flow method for the voltage source converter. Meanwhile
we discussed the node equivalent processing method with VSC station master-slave and droop control mode. VSC station was treated as dummy generator in AC power flow
and three-phase unbalance method was used. Simulation results on IEEE 13 node test system show that the proposed method can flexibly handle master-slave and droop control mode of hybrid AC/DC power distribution system and fast convergence
moreover
VSC-MTDC can effectively reduce the influence of voltage distribution and three-phase unbalance caused by distribution generator. The three-phase unbalance compensation and operation optimization of hybrid AC/DC power distribution system may be further researched based on the results in this paper.