刘剑, 范春菊, 邰能灵. 用于高压直流输电线路的新型横差保护方法[J]. 高电压技术, 2016,42(7):2266-2274.
LIU Jian, FAN Chunju, TAI Nengling. Novel Transverse Differential Protection Method for HVDC Transmission Line[J]. 2016, 42(7): 2266-2274.
为提高双极直流输电线路单端保护的可靠性和速动性
提出了一种基于特定频率电流的横差保护方法。首先
基于直流滤波环节的阻抗特性
选取特定频率电流;然后利用直流线路故障谐波计算模型
分析了直流线路区内、外故障时
直流分流器处特定频率电流及其横差值的特征。分析研究发现
区内故障时
可能出现的特定频率电流横差值的最小值明显大于区外故障时的特定频率电流横差值;利用该特征构造了直流线路区内、外故障判据;此外
还发现单极线路故障时
故障极线路分流器处特定频率电流比非故障极的大
利用该特征提出了一种故障选极方法。由于该保护方法采用600 Hz的频率电流作为保护判据
因此理论上2 k Hz的采样频率即可满足保护需求;该保护采用特定频率电流横差值实现故障判别
克服了传统仅利用单端暂态谐波电流幅值的保护无法区分线路末端和区外故障的缺陷。仿真结果表明
该保护方案能可靠地区分区内、外故障
实现故障类型判别
且在一定的不对称运行方式下同样适用。
In order to improve the reliability and rapidity of single-end protection for bipolar HVDC transmission line
we proposed a transverse differential protection method. Firstly
the specific frequency harmonic current was selected based on the impedance characteristics of DC filter. Based on the equivalent harmonic calculation circuit for DC transmission system
the features of specific frequency harmonic currents and their transverse differential values during internal and external faults were analyzed subsequently. The results show that the minimum transverse differential value for internal fault is obviously higher than that of external fault
which is employed as a fault criterion to identify external fault from internal fault in this paper. In addition
the harmonic current on faulted line is significantly larger than that on non-faulted line
by which a pole selection method is proposed. Since 600 Hz current is used as fault criterion
a sample frequency of 2 k Hz will meet the requirements of the proposed protection. By employing the transverse differential method to achieve fault detection
the shortages that fault at DC line terminal and external fault cannot be identified by the traditional protections based on sing-end harmonic current are overcome. The simulation results show that the proposed protection scheme can identify internal and external faults reliably
and it is able to select the faulted pole. Moreover
the proposed protection scheme can also be applied in the situations with asymmetric operation modes.