ZHOU Kai, ZHAO Qingjie, WU Ke, et al. Effect of High Frequency Harmonics in Traction Locomotives on Hot-spot of Cable Terminations[J]. 2016, 42(11): 3601-3606.
ZHOU Kai, ZHAO Qingjie, WU Ke, et al. Effect of High Frequency Harmonics in Traction Locomotives on Hot-spot of Cable Terminations[J]. 2016, 42(11): 3601-3606.DOI:
To investigate high frequency harmonics in traction locomotives and its fast degraded problems of insulation for stress control type cable terminations
this paper discusses the changes of the distortion rate of voltage and the harmonics in power grid when the traction locomotives are passing neutral section
and the effect of high frequency harmonics on cable termination is also discussed. The experimental setup of high frequency and high voltage aging is installed
and the high voltage is applied to the cable terminations with the different frequencies
and an infrared thermal image instrument is used to analyze the effects of high frequencies on the hot spots for the different cable terminations. According to the results
when the locomotive is passing neutral section
the fluctuations of voltage and current in power grid are noticeable
which can result in severe harmonics. With the increase in the harmonic frequency
cable termination forms the higher electric field on the spot
which can transform resistive heating. For this reason
the resistive thermal power density also increases with the increase in frequency
and the temperature rise of hot spot on the stress control type cable termination is much higher than that of geometric control type cable termination. Increase of harmonic frequency will lead to degradation of the dielectric performance
and it will cause the increase of electric field strength cable termination
installing properly high frequency filter devices for traction locomotives contributes to prolong service life of that electrical equipment.