GOU Ruifeng, MA Zhenjun. Different Protection Tactics for Electric Triggered Thyristor and Light Triggered Thyristor Valve About Reverse Recovery Period[J]. 2016, 42(12): 3982-3988.
GOU Ruifeng, MA Zhenjun. Different Protection Tactics for Electric Triggered Thyristor and Light Triggered Thyristor Valve About Reverse Recovery Period[J]. 2016, 42(12): 3982-3988.DOI:
ETT and LTT thyristor valves have some problems and defects at the protection of the thyristor reverse recovery period in the operation expreince of HVDC project
even results in the forced outage of converter. We analyzed and researched the protection tactics of the thyristor valve at the reverse recovery period
and analyzed the defect of dead zone caused by misjudge
malfunction or delay in the protection during operation. For ETT valves
the main reason is that direct du/dt detection is not used. For LTT valves
they are non dual-configuration without any feedback detection. Therefore
du/dt protection is adopted directly in ETT valves
and a double design and feedback detection are adopted for RPU of LTT valves as optimization. Furthermore
we put forward a new idea for domestic production with a more accurate and effective way for the key protection.