LI Qingmin, LIU Sihua, WANG Jian, et al. Characteristics of Partial Discharges Caused by Free Metal Particle and Influencing Factors in DC Gas Insulated Line[J]. 2017, 43(2): 367-374.
LI Qingmin, LIU Sihua, WANG Jian, et al. Characteristics of Partial Discharges Caused by Free Metal Particle and Influencing Factors in DC Gas Insulated Line[J]. 2017, 43(2): 367-374.DOI:
直流气体绝缘线路中自由金属微粒的局部放电特性与影响因素
摘要
直流气体绝缘线路(GIL)中的自由金属微粒会使电场发生畸变
使绝缘气体/绝缘子发生局部放电等劣化效应。为此
研究了微粒局部放电的影响因素以及严重程度
在密封同轴圆柱腔体内充入不同气压的SF6气体
以不同长度的线形微粒进行了试验
利用脉冲电流法及高速相机同时观察了其局部放电信号与微粒运动行为
对局部放电信号的平均局部放电量、平均局部放电时间间隔进行了分析。结果表明:对于自由线形金属微粒
微粒的平均局部放电量与长度、最大可能带电量成正相关
可根据微粒的局部放电信号判断其危险程度及微粒长度;在负电压下
微粒跳起运动至高压电极附近
发生"飞萤"现象;在正电压下
微粒在外壳地电极跳起后落至地电极
并不断弹跳;且微粒在负电压下的平均局部放电量是在正电压下的2
5
倍
平均局部放电时间间隔较小;随着气压增大
气体的平均局部放电量随之减小
但有趋于饱和的趋势。因此
自由金属微粒的局部放电特性可以为金属微粒的严重程度判别与故障诊断提供依据。
Abstract
Free metal particle within DC gas insulated line(GIL) greatly threatens the insulation system by distorting the electric field and inducing partial discharge in insulation gas or on insulator surface. To investigate the severity of free particle on insulation and influencing factors
we establish a coaxial cylindrical electrode system filled with SF6 of different pressures
in which line-shape free particles of different lengths are set.Meanwhile
the partial discharge signal is measured with pulse current method and motion behavior is observed with a high speed camera. Then
the average amplitude and time interval of partial discharge are analyzed. The investigation shows that the average p
artial discharge amplitude is proportional to the particle length and the maximum charge attached to the particle. Thus
the partial discharge signal can be used to assess the severity and length of the particle. When the central electrode is of negative voltage
the particle bounces up
as a "firefly"
in the region close to high voltage electrode. Particle bounces from the ground electrode and then falls down to the ground electrode as a circular motion when the central electrode is positive. The average amplitude of partial discharge under negative voltage is roughly 2
5
times that under positive voltage while the time interval is less. The activity of partial discharge decreases with increasing the SF6 pressure and has a saturated tendency. Therefore
the characteristics of partial discharge caused by free metal particles can provide a basis for researching the severity of particle on insulation and fault recognition.