WANG Jian, ZHANG Guangzhou, ZHAO Xiaozhen, et al. Online Detection Investigation of the High Voltage Shunt Reactor Winding Deformation Based on Coupling Injection of Pulses[J]. 2017, 43(3): 872-878.
WANG Jian, ZHANG Guangzhou, ZHAO Xiaozhen, et al. Online Detection Investigation of the High Voltage Shunt Reactor Winding Deformation Based on Coupling Injection of Pulses[J]. 2017, 43(3): 872-878.DOI:
The online detection of winding deformations is seldomly investigated so far.Therefore
we proposed a detection method system of the high voltage shunt reactor winding deformation based on the impulse coupling injecting analysis
and the corresponding system is developed.Then
the detection system is verified and installed in 750 k V high voltage shunt reactor of a certain substation.It is concluded from the obtained frequency response characteristics of threephase high-voltage shunt reactors that the response voltage of 300 m V can be obtain under the excitation pulse voltage of 500 V; and the fingerprint data are obtained to provide the basis of the condition monitoring and warning of the windings.The reliable operation of power grid will be promoted if the proposed method is applied widely.