LI Jinzhong, ZHANG Dandan, XU Zhengyu, et al. Heat Dissipation Performance of Ultra-high Voltage Shunt Reactor with Sound Insulation Based on Finite Element Method[J]. 2017, 43(3): 822-827.
LI Jinzhong, ZHANG Dandan, XU Zhengyu, et al. Heat Dissipation Performance of Ultra-high Voltage Shunt Reactor with Sound Insulation Based on Finite Element Method[J]. 2017, 43(3): 822-827.DOI:
The noise of an ultra-high voltage shunt reactor is becoming more and more prominent.In order to reduce the noise of the reactor
a sound insulation device is applied to get large noise reduction.But it may cause reactor heat problem and its internal temperature rise.High temperature will degrade the insulation system performance
and have an impact on the operation reliability and economic performance of the reactor.It is necessary to study the heat dissipation of shunt reactor with sound insulation device.Consequently
using the finite element method
we established a model of UHV shunt reactor to simulate the process of heat production and heat dissipation.Moreover
we studied the heat dissipation performance
the temperature distribution
and the temperature rise before and after the installation of sound insula
tion device.The simulation results are in good agreement with the experimental ones
the internal temperature of the reactor is increased only 2
3
K after installation of sound insulation device
but it will not affect its stable operation.The heat dissipation of the reactor is mainly determined by the circulating flow of the insulating oil.Under the premise of good heat dissipation performance of the reactor
the installation of the sound insulation device will not significantly affect the temperature rise.