SHEN Yufeng, LIANG Xidong, WANG Jiafu, et al. Pollution Characteristics of AC 500 kV Composite Cross-arm in High Altitude Area[J]. 2017, 43(8): 2760-2768.
SHEN Yufeng, LIANG Xidong, WANG Jiafu, et al. Pollution Characteristics of AC 500 kV Composite Cross-arm in High Altitude Area[J]. 2017, 43(8): 2760-2768.DOI:
高海拔下交流500 kV复合横担污闪特性
摘要
复合横担杆塔的应用对节省输电走廊等资源具有重要意义。500 k V复合横担由2支呈"V"形布置的水平大直径绝缘子和2支斜拉绝缘子构成。为获得500 k V复合横担的污闪特性
在高海拔下
对全尺寸500 k V复合横担大直径水平部分进行了多个污秽度下的人工污秽试验
研究了污闪过程中的局部电弧电流及电弧发展过程
并校核了500 k V复合横担的污秽外绝缘配置裕度。研究结果表明:高海拔下复合横担污闪电压与污秽度呈负幂指数关系;随着污秽度的增加
The application of composite cross-arm tower which saves the transmission corridor will be of a great significance. The 500 k V composite cross-arm comprises of two horizontal large size composite insulators which are arranged in "V" structure and two tensile composite insulators which are arranged in inclination position. In order to obtain the pollution characteristics of 500 k V composite cross-arm
we performed the pollution tests of full-scale AC 500 k V unilateral composite cross-arm with several pollution degree under the high altitude condition. Synchronously
the partial arc current and the flashover development process of pollution test were also studied. And the pollution outdoor insulation configuration margin of 500 k V composite cross-arm was verified. The results indicate that the 50% flashover voltage of unilateral composite cross-arm presents a negative power relationship with pollution degree. The biggest partial arc current increases approximately in linearity form with the pollution degree at the 50% flashover voltage. The sporadically discharge and partial arc discharge appear at the bottom side of the large diameter insulator more easily. The 50% flashover voltage of bilateral composite cross-arm is lower than that of unilateral by approximately 3%
and the partial arc alternately appears at the bilateral composite cross-arm. The 500 k V composite cross-arm has a relatively high pollution insulation configuration.