ZHENG Yuesheng, CHEN Yong, ZHONG Xiaoyan, et al. Effects of Barrier Dimensions on AC Withstand Characteristics of Air Insulated Rod-plane Gaps[J]. 2018, 44(1): 195-200.
ZHENG Yuesheng, CHEN Yong, ZHONG Xiaoyan, et al. Effects of Barrier Dimensions on AC Withstand Characteristics of Air Insulated Rod-plane Gaps[J]. 2018, 44(1): 195-200.DOI:
隔板尺寸对棒-板空气绝缘间隙工频耐压特性的影响
摘要
为了进一步揭示隔板尺寸对气体绝缘间隙耐压水平的影响
对棒-板空气绝缘间隙引入不同尺寸隔板前后的工频耐压特性进行了实验研究。通过改变隔板位置和电极开距
研究了不同尺寸隔板对间隙工频击穿电压和起晕电压的作用
并分析了隔板表面的剩余电荷对击穿电压的影响。结果表明:隔板的引入大大提高了整个间隙的击穿电压
隔板尺寸较大时击穿电压最大可提高到原来的2.32倍;隔板的引入会略微降低整个间隙的起晕电压
最大下降幅值约为2 k V;隔板表面的剩余电荷对工频击穿电压通常不存在累积效应。为使整体工频耐压特性最佳
需要综合考虑隔板的尺寸和位置对击穿电压和起晕电压的作用。
Abstract
In order to further reveal the influences of barrier dimensions on the withstand voltage levels of gas insulated gaps
we experimentally investigated the AC withstand characteristics of air insulated rod-plane gaps before and after introducing the barriers of different dimensions.Moreover
by varying different barrier positions and gap distances
we investigated the barrier effects with different dimensions on the AC breakdown voltages and corona onset voltages
as well as the effects of the residual charges on barrier surfaces on the breakdown voltages.The results show that the breakdown voltage is significantly increased by the presence of a barrier.With a large barrier inserted
the breakdown voltage level is even increased up to about 2.32 times of that without a barrier.The corona onset voltage is slightly decreased under the effect of the barrier with a maximum decreased voltage about 2 k V.The residual charges on barrier surfaces always have no accumulative effect on the breakdown voltages.In order to achieve the best performances concerning to the global AC withstand characteristics
the effects of barrier dimensions and positions on the breakdown voltages and corona onset voltages should be synthetically considered.