Analysis on the Characteristics of Short-tail Voltage Wave of Insulator on the Double-circuit Transmission Line in Back Flashover and Design of the Experiment Circuit
HAN Yongxia, RUAN Yaoxuan, ZHANG Yaqi, et al. Analysis on the Characteristics of Short-tail Voltage Wave of Insulator on the Double-circuit Transmission Line in Back Flashover and Design of the Experiment Circuit[J]. 2018, 44(3): 772-778.
HAN Yongxia, RUAN Yaoxuan, ZHANG Yaqi, et al. Analysis on the Characteristics of Short-tail Voltage Wave of Insulator on the Double-circuit Transmission Line in Back Flashover and Design of the Experiment Circuit[J]. 2018, 44(3): 772-778.DOI:
Lightning is the main reason for the trip of transmission line
however
the lightning flashover criterion based on standard lightning impulse has some limitations in back flashover criterion calculation
thus it is necessary to research the simulation and experiments on the short-tail voltage wave under transmission line back flashover. Based on the PSCAD/EMTDC simulation software
we established a back flashover model of the 110 k V double-circuit transmission line.Meanwhile
we simulated and analyzed the influences of the tower height
lightning current model(double exponential wave and heidler wave) and gro
unding resistance on the waveforms. Based on the present impulse voltage generator in the laboratory
the impulse voltage circuit that meets the requirement of different short-tail voltage waveform was designed
and the experiment was carried out. The results of simulation show that the wavefront of short-tail voltage wave is shorter if towers are higher. The peak
the wavefront
and the wavetail decrease obviously with the decrease of grounding resistance
and the short-tail voltage wave generated by double exponential current is different from that generated by heidler current. In addition
the wavefront is between 0.2
2
.0 μs and the the wavetail mainly focuses on 5
1
0 μs. The experimenal results show that the insulator U50% under short-tail voltage wave is higher than that under standard lightning wave by 25%
3
0%
which shows that the backflashover criterion under these two kinds wave has a large difference
thus the waveform of impulse voltage greatly influences the backflashover withstand calculation result.