LIU Bin, YE Guoxiong, TONG Yue, et al. Influence of Disconnector in Gas Insulated Switchgear Switching On/Off on Electromagnetic Compatibility of Electronic Transformer[J]. 2018, 44(4): 1204-1210.
LIU Bin, YE Guoxiong, TONG Yue, et al. Influence of Disconnector in Gas Insulated Switchgear Switching On/Off on Electromagnetic Compatibility of Electronic Transformer[J]. 2018, 44(4): 1204-1210.DOI:
气体绝缘开关设备的隔离开关分合操作对电子式互感器电磁兼容特性的影响
摘要
为深入研究气体绝缘开关设备(GIS)隔离开关分合操作对电子式互感器电磁兼容特性的影响
研究了隔离开关操作过程中电磁干扰信号对电子式互感器影响的大小与各种耦合途径
建立了基于500 kV GIS隔离开关分合操作的电子式互感器电磁兼容试验系统。利用开发的试验系统
对500 kV GIS隔离开关操作产生的暂态过程进行实地测量
并对系统中接入的电子式互感器进行输出测试。试验系统获得了VFTO和VFTC的典型波形、隔离开关间隙的击穿电压特性和燃弧规律以及电子式互感器典型故障。结果表明:该试验回路产生的VFTC幅值最大值为826.8 A
To investigate the influences of disconnector in gas insulated switchgear(GIS) switching-on/off on electromagnetic compatibility of electronic transformer
we investigated the influence level and coupling paths of multiple electromagnetic disturbances on electronic transformer
and developed an electromagnetic compatibility testing system of electronic transformer based on 500 kV GIS disconnector switching.The testing system can measure transient process induced by 500 kV GIS disconnector switching-on/off and output waveform of electronic transformer simultaneously.Typical waveforms of VFTO and VFTC
breakdown voltage characteristics
the arcing law of the disconnector
and typical faults of electronic transformer can be obtained in this testing system.The VFTC has its highest amplitude of 826.8 A
with a rising rate about 6.51 kA/μs.The VFTO has its maximun overvoltage multiple of 1.22
with a rising rate about 17.2 kV/μs.Testing results prove that the transient measurement results accord with theoretical expectation
and reflect the real situation of transient process exactly.There are significant differences between IEC standard of electronic transformer and electromagnetic environment in substations.Anti-interference ability of the transformers can be improved effectively by proposing anti-interference measures according to different coupling approaches.