LI Runchang, LIU Hongshun, LOU Jie, et al. Investigation on Electrical Characteristics and Arc Column Morphology of Secondary Arc on UHV Transmission Lines[J]. 2018, 44(4): 1359-1366.
LI Runchang, LIU Hongshun, LOU Jie, et al. Investigation on Electrical Characteristics and Arc Column Morphology of Secondary Arc on UHV Transmission Lines[J]. 2018, 44(4): 1359-1366.DOI:
In order to investigate the electrical characteristics of the voltage-current and the morphologic development of secondary arc
we built a low-voltage simulative experimental platform of secondary arc for UHV transmission lines without compensation.On the basis of the experimental platform
the electrical characteristics of the voltage and current were analyzed
involved with development rules of transient process
discharge power
and discharge energy of the secondary arc.When the secondary arc current is 10 A and 30 A
the maximum range of discharge power is in the range of 2
3
MW and its duration is about 0.27
0
.38 s.When the discharge is over
the discharge energy of 10 A or 30 A secondary arc is greater than 9×10
9
J.In addition
binary mask image was processed
and the centroid
the arc length and the arc radius of the secondary arc were also analyzed.The centroid trajectory quantitatively describes the movement of the arc column
on the basis of the centroid trajectory and the force analysis of current element in cascaded chain model for secondary arc
the secondary arc shifts overall horizontally under the effect of the electromagnetic force and rises vertically mainly under the effect of the thermal buoyancy.By comparing the experimental results and computational results
the arc length does not exceed the corresponding maximum computation value of the arc length at arc extinction time.The experimental results of the arc radius is also consistent to its computation results in the order of magnitude.