LU Yao, ZHANG Yemao, LIU Zhenhuan, et al. Study on Standing Wave of “100 Hz” Pure Tone from UHV AC Double-circuit Transmission Lines on the Same Tower[J]. 2018, 44(7): 2261-2267.
LU Yao, ZHANG Yemao, LIU Zhenhuan, et al. Study on Standing Wave of “100 Hz” Pure Tone from UHV AC Double-circuit Transmission Lines on the Same Tower[J]. 2018, 44(7): 2261-2267.DOI:
The ‘100 Hz’ pure tone(hum) from the power transmission line is remarkable in rainy day
and has an increasing risk in high-altitude areas. In order to prevent the residential area from the crest area of the standing wave
we studied the standing wave distribution of ‘100 Hz’ pure tone. According to the ‘generation’ of hum under the condition of the heavy rain proposed by American EPRI
considering the ground reflection of sound waves and interference between the sound waves
we established a computational model of standing waves of the pure tone and obtained a distribution rule. Statistical analysis of ‘100 Hz’ pure tone test data is made under heavy rain conditions
and compared with the calculation results. The calculation results show that
unlike A-weighted sound level
the distribution of ‘100 Hz’ pure tone of double circuit lines on the same tower with inverse phase sequence is asymmetric and vibration attenuated. The attenuation speed is slower than that of A-weighted sound level; Near transmission lines
the distance between the adjacent peaks is smaller; far from transmission lines
the distance between the adjacent peaks is increased. The value of amplitude decreases monotonically several hundred meters away from transmission lines.