LI Chao, HU Wenwang, TANG Zhijun, et al. Control Strategy of Power Transfer in Bipolar HVDC Flexible Transmission System[J]. 2018, 44(7): 2173-2180.DOI:
If single-pole faults occur in bipolar HVDC flexible transmission system
the power can be transferred to the normal pole quickly
and the influence of load shedding on the stability of the power grid is reduced. In order to ensure that the power transfer can be successfully completed
firstly
we put forward the feasibility conditions and the process of power transfer; secondly
we established a real-time digital simulation model during the power transfer process
analyzed the electrical characteristics of DC field
and proposed an optimization method of power transfer rate
finally
a designed example was given and the verification tests were conducted at Xiamen HVDC flexible transmission project. The test results show that the direct current rising speed is limited by reactor and cable
so the power can not be transmitted in time and accumulated in the modular multilevel converter
which can lead to DC overvoltage protection action. When the power transfer rate is 500 MW/10 ms
the DC overvoltage Ⅰ segment protection action is caused. When the power transfer rate is optimized by using the numerical valued of 500 MW/60 ms
the power transfer process is successfully completed. Based on the analysis of the electrical characteristics of DC field
the power transfer is successful implemented in a Xiamen HVDC flexible transmission project by optimizing the power transfer rate
which proves the feasibility of control strategy of power transfer process in bipolar HVDC flexible transmission system..