RUAN Ling, ZHAO Aixuan, DENG Dan, et al. Influence of Unbalanced Current in 3-core Power Cable on Temperature Distribution[J]. 2018, 44(8): 2704-2709.DOI:
When 3-core distribution power cable is in service
unbalanced current in 3-phase usually occurs due to the different demands of consumers load in different phases. As a result
it is necessary to determine the cable temperature rise under unbalanced current. Only balanced conditions of 3-phase current are considered in IEC 60287 and the thermal circuit method is too difficult to calculate temperature rise. Therefore
we applied a finite element method to build a numerical model for cables’ thermal field. Using the cable thermal field model
we set different unbalanced degrees in phase-A and calculated the greatest load current of phases-B and phases-C by dichotomy. According to the results
if the further unbalanced degree deviates from 0 value
the total current of cable transmitting under 90 ℃ is less. Besides
the total loss of cable is smallest when the unbalanced degree is 0.6. Distribution administrator can make use of different unbalanced degrees to decrease the line loss rate and increase the cable utilization ratio.