HE Ruiqin, YANG Ning, CUI Chenggang, et al. Passivity-based Control Method of Mid-point Capacitor Three-phase Four-wire Shunt Active Power Filter Based on PCHD Model[J]. 2018, 44(10): 3266-3274.
HE Ruiqin, YANG Ning, CUI Chenggang, et al. Passivity-based Control Method of Mid-point Capacitor Three-phase Four-wire Shunt Active Power Filter Based on PCHD Model[J]. 2018, 44(10): 3266-3274.DOI:
It is required for a three-phase three-wire shunt active power filter(SAPF) to control the positive
negative and zero sequence components respectively when the power grid is not balanced
therefore
taking the mid-point capacitor three-phase four-wire SAPF as the research object
we proposed a nonlinear passivity-based control(PBC) strategy based on port-controlled hamilton with dissipation(PCHD) model by using its passivity.Firstly
according to the mathematical model of the controlled object in the dq0 coordinate system
the PCHD model was obtained. Then
the passive controller of SAPF was designed by an interconnection and damping assignment(IDA) method. Finally
the outer-loop voltage controller of SAPF based on PI control was obtained according to the close connection between the total and differential voltages of the DC side and compensating current. Simulation and experimental results show that the mid-point capacitor three-phase four-wire SAPF based on PCHD model designed in this paper can realize low harmonic current
DC side voltage stability and neutral-point voltage balance on the condition of balanced or unbalanced grid;compared to the traditional PI control
the proposed control method has a better compensation effect and faster response speed.