陶风波, 王帅, 贾勇勇, 等. 特高压气体绝缘金属封闭式组合电器的现场冲击耐压试验方法[J]. 高电压技术, 2018,44(12):3936-3943.
TAO Fengbo, WANG Shuai, JIA Yongyong, et al. Method of On-site Tests for the Withstand Voltage of Ultra-high-voltage GIS Lightning Impulse[J]. 2018, 44(12): 3936-3943.
气体绝缘金属封闭式组合电器(GIS)的现场冲击耐压试验能够更有效地检测出金属尖刺、绝缘子断裂等集中性缺陷
已成为设备现场耐压试验的重要组成部分。为此针对1 000 kV淮南—南京—上海交流特高压南京变电站1 100 kV GIS现场雷电冲击耐压试验工程
利用ATP-EMTP电磁暂态分析软件对特高压GIS现场冲击耐压试验系统进行建模
并研究了特高压GIS现场冲击耐压试验方式的选取与试验条件对电压波形的影响。研究结果表明:当负载电容C
t
<
7 000 pF时
能够通过调节波前电阻使负载电压满足标准雷电波要求
当负载电容C
t
>7 000 pF时
无法得到标准雷电波;接入单台断路器的方式试验电压波形质量高
试验工作量大;接入多台断路器的方式试验效率高
但需降低对试验电压波形的要求。接入外置分压器会使电压幅值略微下降、波前时间增加;套管间高压引线长度增加会使波前时间略有缩短
并导致负载电压波形出现振荡
引线长度取20 m较为合适。
On-site tests for the withstand voltage of lightning impulse of gas-insulated metal-enclosed switchgear(GIS)
which can effectively detect concentrative defects
has become an important part of GIS on-site withstand voltage tests. Therefore
we developed a model for the system of testing the withstand voltage of ultra-high-voltage GIS on-site lightning impulse by the ATP-EMTP transient analysis software based on the 1 100 kV GIS on-site withstand voltage test project of 1 000 kV Nanjing Ultra-high-voltage Substation. Moreover
we investigated the influences of test schemes selection method and the test conditions on the voltage waveform. The results show that the standard lightning impulse voltage waveform can be generated by regulating the wavefront resistance when the load capacitance is smaller than 7 000 pF; however
when the load capacitance is greater than 7 000 pF
the standard lightning impulse cannot be obtained. If the single-circuit-breaker connecting mode is adopted
we can get a higher waveform quality
but the efficiency is relatively lower. If the multi-circuit-breaker connecting mode is adopted
higher efficiency can be acquired at the expense of waveform quality. The introduction of external voltage divider will slightly decrease the voltage amplitude and make the wave-front time longer. As the length of high voltage wire between bushing increases
the wave-front time is slightly shortened
and simultaneously causes the oscillation of load voltage waveform. Thus
the 20 m-long wire is suggested to be adopted.