QIAN Yong, ZHANG Yue, LIU Wei, et al. Simulation on the Propagation of the Optical Signal of Partial Discharge in T-shaped GIS Model[J]. 2019, 45(5): 1510-1517.
QIAN Yong, ZHANG Yue, LIU Wei, et al. Simulation on the Propagation of the Optical Signal of Partial Discharge in T-shaped GIS Model[J]. 2019, 45(5): 1510-1517.DOI:
T型GIS模型中局部放电光学信号传播特性仿真
摘要
为了研究T型气体绝缘开关设备(GIS)腔体中局部放电光学信号传播特性
通过建模仿真
在不同放电位置、探测距离以及探测角度条件下
观察并分析了各个探测面上的光学信号。结果表明:1)不同放电位置情况下
GIS部件的遮挡使探测面的光斑产生暗区
减弱了探测面和探测点的光学信号强度;2)经过T型转角后
探测面位置距离放电源越远
光学信号越弱
以放电源位于x轴正方向50 cm(即x50)为例
距离放电源75 cm的平均相对辐照度是50cm时的44.31%;3)探测角度不同时
放电源直射出来的相对辐照度值较大
而被部件遮挡或者直射光较弱的探测点的值较小。以T型转角上的C1探测面
x50为放电源为例
当探测角度为270°时相对辐照度值最大
225°时最小
仅为前者的39.02%。
Abstract
In order to study the propagation characteristics of partial discharge optical signals in T-type GIS cavities
the optical signals on each detection plane are observed and analyzed under the conditions of different discharge positions
detection distances and angles by modeling and simulation. The results show that: 1) In the case of different discharge positions
the occlusion of the GIS component enables the light spot on the detection plane to generate a dark area
reducing the optical signal strength of the detection plane and the detection point. 2) After T-shaped cornering
the farther the power source is away from
the weaker the optical signal will be. The x50
namely
the discharge source is set at x=50 cm
is taken as an example
it is revealed that the average relative irradiance decreases to 44.31% when the distance from the discharge source is 75 cm is compared to when the distance is 50 cm. 3) When the detection angle is different
the relative irradiance value of the detection point of direct ray is relatively large
and the value of the detection point which is obscured by the component is relatively small. The C1 detection surface and x50 coordinates on the T-type angle are taken as examples
it is revealed that the relative irradiance is largest when the detection angle is 270 degrees
and the relative irradiance is smallest when the detection angle is 225 degrees