WANG Liming, FU Kaiwei, MEI Hongwei, et al. Influence of Environmental Humidity on Infrared Measurement Temperature of Composite Insulators[J]. 2019, 45(6): 1955-1961.
WANG Liming, FU Kaiwei, MEI Hongwei, et al. Influence of Environmental Humidity on Infrared Measurement Temperature of Composite Insulators[J]. 2019, 45(6): 1955-1961.DOI:
环境湿度对复合绝缘子红外测温的影响
摘要
红外测温技术是检测复合绝缘子端部发热的常用手段。在目前使用过程中
红外测温结果受自然环境特别是环境湿度的影响较大。对深圳地区近5年的部分红外测温数据进行统计分析
研究复合绝缘子高压端与低压端温差测量值与环境相对湿度的相关性
并在不同环境相对湿度下对复合绝缘子的性能进行试验分析。结果表明:在较高环境相对湿度条件下
复合绝缘子红外测温结果上升
介损角正切值逐步增大并趋于饱和。结合数据统计和试验结果
建议红外测温技术使用应在环境湿度低于67.5%时进行。
Abstract
The infrared temperature measurement technology is often used for detecting the terminal heating of composite insulator. Currently
in the process of measurement
the natural environmental factors
especially the environment humidity
plays an important role in effecting the measured results. Therefore
we statistically analyzed the recent 5 years data of infrared temperature measurement in Shenzhen
and studied the correlation between the environment humidity and measured value of temperature difference between the high-voltage and low-voltage terminals of the composite insulator under different environment relative humidity. Moreover
we analyzed the properties of composite insulator under different environment humidity by tests. The results show that
under the condition of higher environment relative humidity
the measured value of composite insulator will rise
the tangent value of dielectric loss angle gradually increases and trends to be saturated. According to the statistical data and test results
we recommend that the infrared temperature measurement shall be conducted when the environment humidity is lower than 67.5%.