WANG Yuan, WANG Yuhong, WANG Biao, et al. Influence of DC Asynchronous Interconnection on Damping Characteristics of Sending System[J]. 2019, 45(7): 2150-2159.
WANG Yuan, WANG Yuhong, WANG Biao, et al. Influence of DC Asynchronous Interconnection on Damping Characteristics of Sending System[J]. 2019, 45(7): 2150-2159.DOI:
Asynchronous grid interconnection in which a flexible HVDC system is adopted can eliminate the inter-area oscillations in large interconnected systems. However
the oscillations inside the sending end system may be affected. To explore the composition and variation of low frequency oscillation damping of sending end in the cases of AC and flexible dc interconnection
firstly
we analyzed the effects of system load
tie line flow
operating voltage and impedance on system damping in detail. Secondly
taking the addition of flexible DC system on AC tie into account
we derived a system damping expression corresponding to different control mode and installation position of DC converter. Thereby
the variation mechanism of low frequency oscillation characteristics and small disturbance stability of sending end system was revealed
and PSASP simulation was used to verify these theories. The results show that the flexible DC interconnection can clear the inter-area low frequency oscillation
improve the damping characteristics and small disturbance stability of sending end system
but it may change the oscillation mode inside the area.