LI Jian, WANG Biao, LIU Chengzhuo, et al. Suppression Scheme for Ultra-low Frequency Oscillation Based on Frequency Limit Controller[J]. 2019, 45(7): 2126-2133.
LI Jian, WANG Biao, LIU Chengzhuo, et al. Suppression Scheme for Ultra-low Frequency Oscillation Based on Frequency Limit Controller[J]. 2019, 45(7): 2126-2133.DOI:
With the developmment of Luxi Back-to-Back HVDC project and Yu’e Back-to-Back HVDC project
ultra-low frequency oscillation becomes a serious threat to the stability of power system. For an asynchronous interconnection multi-send HVDC system
the mechanism of ultra-low frequency oscillation and suppressing ultra-low frequency oscillation by FLC(frequency limit controller) is analyzed. Considering the distribution of hydropower in the sending end
a new DC sorting method is proposed
which combines the influences of DC power change on AC system and sensitivity of ultra-low frequency oscillation mode. Based on the results above
a new suppression scheme is proposed. In order to achieve a better suppression effect
the multi DC optimization problem is transformed into multiple single-DC sequential optimization problems in the scheme by TLS-ESPRIT(total least squares-estimation of signal parameters via rotational invariance techniques) and improved PSO(particle swarm optimization). Finally
the effectiveness of the scheme is verified by simulation results of Sichuan-Chongqing power system which already has an asynchronous interconnection with Hubei power system.