WU Ji, WANG Zengbin, Lü Hong, et al. Calculation of GIS Temperature Rise Considering Effect of Gas Flow and Experimental Study[J]. 2020, 46(3): 815-823.
WU Ji, WANG Zengbin, Lü Hong, et al. Calculation of GIS Temperature Rise Considering Effect of Gas Flow and Experimental Study[J]. 2020, 46(3): 815-823.DOI:
It is very important to precisely calculate the temperature rise of GIS
which may aid the optimization design
shorten the development duration and reduce the development cost. For one 126 kV three-phase-in-one-tank type GIS
taking the contact resistance
proximity and skin effects
and eddy current effect into account
we firstly developed an electromagnetic – thermal coupled model
and then analyzed the loss distribution and temperature rise characteristics under the action of 2 200 A current. In order to further investigate the influence of gas flow
we proposed an electromagnetic – thermal – fluid coupled model for the GIS model
and compared the temperature rise calculation results based on two difference methods
i.e.
only considering the GIS inner SF
6
fluid domain
or considering both the GIS inner SF
6
fluid domain and GIS outer air fluid domain. According to the relevant national standard requirement
experiments for temperature rise were carried out under the same current of 2 200 A. It is revealed that the loss density of disconnector conductors is higher than that of circuit breaker conductors
the calculation precision of the last method is the highest
and the relative error is less than 10%. The results can provide an effective method for optimization design of thermal characteristics of GIS
and technical references for other power equipment.