ZHANG Dongdong, NI Xijun, CHENG Guilin, et al. Pollution Distribution Performance of Windward/Leeward Sides of Insulators and Influential Rule on DC Pollution Flashover Voltage[J]. 2020, 46(4): 1353-1360.
ZHANG Dongdong, NI Xijun, CHENG Guilin, et al. Pollution Distribution Performance of Windward/Leeward Sides of Insulators and Influential Rule on DC Pollution Flashover Voltage[J]. 2020, 46(4): 1353-1360.DOI:
Accidents of pollution flashover still exists in certain areas. It is still of practical significance to further study external insulation pollution issues. The field observations have already shown that insulator surface is coated with obvious non-uniform pollution on windward and leeward sides. Lack of systematical research on this phenomenon makes the existing contamination tests and outdoor pollution insulation designs not to fully reflect the actual situations. Consequently
by carrying out fluid dynamic simulation and artificial tests
we studied the pollution distribution performance of the windward/leeward sides of insulator and their influential rule on DC pollution flashover voltage. Research results indicate that the contamination on insulator windward/leeward side is in fan-shape non-uniform distribution
and the non-uniformity may reach 1/10. The function of DC electric field
the increment of wind velocity
and particle diameters will enhance the pollution non-uniformity. Under windward/leeward side non-uniform pollution
insulator flashover voltage will subject to a considerable reduction of about 30%. The research results are of certain reference value for the external insulation design of high voltage transmission lines.