In order to improve the reliability of a DC vacuum circuit breaker(VCB) for high current interruption
a novel current commutation interruption(CCI) scheme was proposed based on the typical forced commutation. The current fall rate before the VCB arc current zero(ACZ) was remarkably reduced by the current shunting of an auxiliary switch conduction and by decreasing the effective commutation current
and an interval of low transient recovery voltage(TRV) came out through the voltage clamping of the auxiliary switch conduction after the VCB ACZ. Thereby
the vacuum gap post-arc dielectric recovery behavior was improved
and the reliable high DC current interruption process would be realized for medium and high voltages. By analyzing the commutation process of the new scheme in detail
the influences of some main parameters
such as the stray inductance of the commutation circuit
the turn-on moment of the auxiliary switch
on the commutation performance and the influence rules were obtained. Finally
the 13 kA CCI test for a fast VCB was carried out. During the test
the VCB current fall rate before ACZ was effectively reduced to about 55 A/μs
which lasted for about 50 μs in total. And the VCB TRV was limited to less than 600 V within about 130 μs after ACZ. The test results verify the practicability and effectiveness of the new scheme.