ZHANG Yang, LIN Weixing, DENG Caibo, et al. Redundant Fault-tolerant Control Algorithm of Star-connected Cascaded STATCOM[J]. 2020, 46(10): 3398-3408.DOI:
星形链式STATCOM的冗余容错控制算法
摘要
传统冗余容错控制方法在改变故障相位时
会引起非故障相变化并带来额外的干扰。为了减少故障保护对非故障相的影响
提高多电平级联STATCOM的可靠性
本文提出了一种优化的冗余容错控制算法。首先根据星形链式STATCOM的方程
研究了冗余容错与中性点偏移的定量关系并分析中性点偏移的影响;然后基于负序电流的闭环控制方法
提出了星形链式STATCOM的优化冗余容错控制算法;最后以仿真和实验验证
对比了传统算法和所提优化算法。实验结果表明
该优化算法改善了冗余容错过程中的暂态性能
将故障暂态电流的不平衡度降低2.4%
而稳态不平衡度仅增加1%;非故障模块电压波动下降13%。所提方法有效提高了STATCOM的可靠性
且在对于可靠性要求较高的高压大功率工业领域更为适用。
Abstract
Non-faulty phases will change and cause additional interference when the traditional redundant fault-tolerant control method is adopted to adjust the faulty phase. In order to reduce the influence of fault protection on non-fault phases and improve the reliability of the multilevel cascaded STATCOM
an optimized redundant fault-tolerant control algorithm is proposed. Based on the equations of star-connected STATCOM
the quantitative relationship between redundancy fault tolerance and neutral point shift is studied and the influence of neutral point shift is analyzed. Then
the optimization of star-chain STATCOM redundant fault-tolerant control algorithm is proposed based on the closed-loop control method of negative sequence current. Finally
the traditional and proposed optimization algorithms are compared through simulation and experiments. The experimental results show that the optimization algorithm can improve the transient performance in the process of redundancy and fault tolerance. The unbalance of the fault transient current will reduce by 2.4%
while the steady-state unbalance will only increase by 1%. The voltage fluctuation of the non-faulty module will drop by 13%. The proposed algorithm can improve the reliability of STATCOM and is more applicable for high-power industrial field with high reliability requirements.