In order to study the characteristics of induced voltages on overhead multiconductor distribution lines due to lightning strike to a tall tower
a two-dimensional finite-difference time-domain(2-D FDTD) algorithm model was proposed to calculate the lightning-generated electromagnetic fields based on the tower transmission line model
the lightning induced voltages on multiconductor distribution lines(horizontal and vertical configurations) were computed by means of the Agrawal coupling model
and the accuracy of the algorithm was verified by comparing with the relevant research results abroad. Moreover
the influence of lightning strike to a tall tower or idea flat ground was compared
and the effects of the distance
tower height
soil conductivity as well as well as the shielding wires were evaluated. The results show that the induced voltages produce obvious waveform oscillation and the amplitude increase significantly when lightning strikes a tower compared with flat ground. For the horizontal and vertical configurations
the peak voltages decrease with increasing distance from the lightning channel and increase with the decrease of the soil conductivity. When the tower height is less than the horizontal distance
the peak voltages are positively correlated with the tower height. In addition
the shielding wires can significantly reduce the induced voltages of the line endpoints
and the middle line and the line closest to the shielding wires of the horizontal and vertical configurations are most shielded
respectively. The research conclusions can provide references for lightning protection design of overhead lines.