XIA Lingfeng, ZHOU Ting, XU Bin, et al. Analysis of Ground Resistance Limitation Value of HVDC Electrode System Under High Soil Resistivity Condition[J]. 2021, 47(5): 1720-1728.
XIA Lingfeng, ZHOU Ting, XU Bin, et al. Analysis of Ground Resistance Limitation Value of HVDC Electrode System Under High Soil Resistivity Condition[J]. 2021, 47(5): 1720-1728.DOI:
IEC standard and DL standard has no specific limitation value on the ground resistance of HVDC electrode system
however
in some oversea projects
this value is limited additionally. When the soil resistivity of electrode site is extremely high
the ground resistance will increase as well. Consequently
we list the ground resistances of plenty of as-built HVDC electrode projects
revealing that some projects can operate normally with ground resistance >0.35 ?. Through theoretical derivation and simulation calculation
we analyze the effects of high ground resistance on the steady-state temperature rise
transient temperature rise
step potential
touch potential
loss
and DC bias of the surrounding transformer. Based on Belo Monte Ⅱ UHVDC project Terminal Rio electrode design case
the conclusion can be drawn that high ground resistance will not influence the stability operation of electrode with reasonable design. The comparison of different design cases reveals that canceling the limitation of ground resistance can save engineering costs without impairing the safe and stable operation of electrodes.