双极短路故障下海上风电MMC-HVDC并网系统的暂态运行特性
摘要
双极短路故障作为最严重的直流系统故障
研究该场景下海上风电模块化多电平换流器型高压直流输电(modular multilevel converter-high voltage direct current
MMC-HVDC)并网系统的暂态运行特性对于系统的断路器配置与控制方案设计有着重要意义。首先分析了直流断路器(direct current circuit breaker
Pole-to-pole short-circuit fault is the most serious DC fault
thus the research on the transient operation characteristics of the offshore wind power generation integration system with modular multilevel converter high voltage direct current(MMC-HVDC) in this scenario is of great significance to breaker configuration and control scheme design of the system. In this paper
firstly
the mechanism of the short-circuit current in converter station was analyzed when direct current circuit breaker(DCCB) was not activated
and a calculation method of the AC and DC short-circuit current on the wind farm side and grid side converter station was proposed. Secondly
the transient characteristics of the voltage and current on the AC and DC sides of the converter station under DCCB control were studied
and the impact of wind farm operation conditions and current-limiting reactance parameters on its transient characteristics were taken into consideration. Finally
the electromagnetic transient model of the whole system was built on the PSCAD/EMTDC simulation platform
and the transient characteristics of the voltage and current in the converter station with or without DCCB control under pole-to-pole short-circuit fault were analyzed by simulation. Research indicates that the proposed short-circuit current calculation method has good accuracy. In addition
the recovery rate of wind farm AC and DC voltage is positively correlated with its active power output after DCCB is activated. The research work provides a theoretical basis for the electrical design and circuit breaker selection of the system
and also lays the foundation for the control scheme during the recovery stage of the system.