XIA Yue, LEI Yuanyuan, LIU Gang, et al. Research and Validation of Saturation Model for Single-phase Four-column Converter Transformer Based on No-load Experiment Data and UMEC Model[J]. 2021, 47(10): 3733-3744.
XIA Yue, LEI Yuanyuan, LIU Gang, et al. Research and Validation of Saturation Model for Single-phase Four-column Converter Transformer Based on No-load Experiment Data and UMEC Model[J]. 2021, 47(10): 3733-3744.DOI:
基于空载试验数据和UMEC的单相四柱换流变压器饱和模型研究和有效性验证
摘要
为了准确快捷地对单相四柱换流变压器进行电磁暂态仿真
提出了一种基于空载试验数据和统一磁路(unified magnetic equivalent circuit
In order to accurately and quickly perform electromagnetic transient simulation of single-phase four-leg converter transformers
this paper proposes a single-phase four-limb converter transformer saturation model based on no-load test data and UMEC(unified magnetic equivalent circuit) model. Based on the UMEC magnetic circuit model
the method of solving the incidence matrix
inductance matrix and core permeance of the single-phase four-limb converter transformer is derived. When considering the saturation of the core
the excitation branch is simulated by the parallel connection of a nonlinear resistance and a nonlinear inductance. Through the no-load test data
the piecewise linearization curves of u–i R and u–i L in the excitation branch are obtained to simulate the core loss and the nonlinearity of the magnetic permeability.The method in this paper is based on the UMEC model
meanwhile
the nonlinearity of the core main column
iron yoke
side column and side yoke magnetic guide as a whole is taken into account
thus the method has the advantages of fast calculation speed
high efficiency and high precision. Finally
the method in this paper is used to simulate and calculate the scaled model and the product-level single-phase four-limb converter transformer under normal operating conditions and DC bias conditions. The comparison with experimental measurements proves that the model has high accuracy.